12713020-003-2 Revision F.01 – January 2007 SSU-2000 Technical Reference 133
Chapter 2 TL1 Reference
Set Alarm Elevation Time Parameters
Set Alarm Elevation Time Parameters
This command sets the time for alarm elevation, from 60 seconds to 500 000
seconds. A setting of 0 (zero) means no elevation for the alarm. When an alarm has
been at MINOR or MAJOR level continuously for ELTIME seconds, then it is
elevated to the next level.
ELTIME may be set for each module or ALL modules, and applies to all alarms
created by the module.
Syntax
SET-PRMTR-ELTIME:[tid]:[aid]:ctag::elevtime;
Related Commands
Retrieve Alarm Elevation Time, on page 37
Parameter Format Description
aid ALL Sets the parameters for all modules.
SxAy Sets the parameters for the specfied module.
elevtime 0 | 60 -
500000
Sets the time after which an alarm is elevated to the next
severity level.