Chapter 2 TL1 Reference
Retrieve TDEV History Data
126 SSU-2000 Technical Reference 12713020-003-2 Revision F.01 – January 2007
Retrieve TDEV History Data
This command returns the Historical TDEV data for a port on a DS1, E1, or Sine
Input module. The Historical TDEV data is the 24-hour TDEV data stored every day
at midnight. There are 99 historical TDEV records stored. The command requires
an aid to identify the input port to report data from. The optional parameters are the
clock identifier and the number of days of MTIE history to be retrieved from the
current day (day 0). If no clock source [CLK-A | CLK-B] is specified, the current
output clock is used.
Syntax
RTRV-DATA-TDEV-HIST:[tid]:aid:ctag[::[clksrc][,count];
Response Format
The response is the complied message followed by the requested data.
^^^"aid:ocrdat,ocrtm,TDEV,clksrc,monval1,.., monval16"<cr lf>
where:
aid = port access identifier
ocrdat and ocrtm = the beginning date and time the data was collected
clksrc = clock used for the measurements
tmper = time period for the measurement data, in seconds
monval = data value for the time period, in nanoseconds. There are 16 monvals
in sequence, and the time periods in sequence are 0.1, 0.3, 0.6, 1.0, 3.0, 6.0,
10.0, 30.0, 60.0, 100.0, 300.0, 600.0, 1000.0, 3000.0, 6000.0, and 10 000.0
Related Commands
Retrieve TDEV Data, on page 124
Parameter Value Description
[aid] S1Ay-z Retrieves the current MTIE history data from the specified
Input port.
[clksrc] CLK-A |
CLK-B
Specifies which clock supplies the MTIE history data.
[count] 1 - 99 Specifies the number of days of MTIE history to retrieve.