EasyManuals Logo

Symmetricom SSU-2000 Technical Reference

Symmetricom SSU-2000
400 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #134 background imageLoading...
Page #134 background image
Chapter 2 TL1 Reference
Set Alarm Level Parameters
134 SSU-2000 Technical Reference 12713020-003-2 Revision F.01 – January 2007
Set Alarm Level Parameters
This command assigns an alarm level to the alarm number specified.
Syntax
SET-PRMTR-ALARM:[tid]:aid:ctag::almnum,level[,errcnt],[clrcnt];
Related Commands
Retrieve All Alarms, on page 42
Parameter Format Description
aid SxAy Sets the alarm level parameters for the specfied module.
almnum Specifies the alarm number to be modified. See Chapter
6, Alarms and Events for a list of alarm numbers.
level IGN
RPT
MIN
MAJ
CRT
Sets the alarm level of the specified alarm number.
errcnt Specifies the start delay time, which is the number of
seconds that the alarm must be present before the alarm
message is issued.
clrcnt Specifies the clear delay time, which is the number of
error-free seconds after the alarm condition is cleared
before the alarm indication is cleared.

Table of Contents

Other manuals for Symmetricom SSU-2000

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Symmetricom SSU-2000 and is the answer not in the manual?

Symmetricom SSU-2000 Specifications

General IconGeneral
BrandSymmetricom
ModelSSU-2000
CategoryPower Supply
LanguageEnglish

Related product manuals