Chapter 2 TL1 Reference
Set Clock AutoReturn
138 SSU-2000 Technical Reference 12713020-003-2 Revision F.01 – January 2007
Set Clock AutoReturn
The command sets the clock mode of returning or not returning after faults are
cleared. The
ar parameter changes the active Clock module selection mode to [ON
| OFF] for revertive or non-revertive operation. See the SSU-2000 User’s Guide for
more information on revertive and non-revertive operation.
Syntax
SET-CLK-AR:[tid]::ctag::ar;
Empty fields leave parameters unchanged.
Related Commands
Retrieve Clock Parameters, on page 46
Retrieve Clock Status, on page 47
Parameter Value Description
[ar] ON Sets the active Clock module to the Revertive mode.
OFF Sets the active Clock module to the Non-Revertive mode.