12713020-003-2 Revision F.01 – January 2007 SSU-2000 Technical Reference 135
Chapter 2 TL1 Reference
Set CC Input Parameters
Set CC Input Parameters
This command sets the parameters on the specified Composite Clock Input module
or port.
Syntax
SET-PRMTR-CCINP:[tid]:[aid]:ctag::[pstate],[pri],[pql],[zs];
Related Commands
Retrieve CC Input Parameters, on page 43
Parameter Format Description
aid SxAy[-z] Sets the parameters for the specfied CC Input module [or
port].
pstate ON | OFF Turns the selected module [or port] on or off.
pri 1 - 10 |
MON
Sets the priority of the specified module [or port]; MON =
Monitor.
pql 1 - 16 Sets the priority quality level of the specified module [or
port].
zs ON | OFF Turns zero suppression on or off for the specified module
[or port].