12713020-003-2 Revision F.01 – January 2007 SSU-2000 Technical Reference 157
Chapter 2 TL1 Reference
Set Keep-alive Parameter
Set Keep-alive Parameter
This command supports a "keep-alive” mode in which, based upon a user settable
time, the SSU-2000 generates an event to alert an upstream support system that
the SSU-2000 and associated communication path is functional.
Syntax
SET-PRMTR-KEEPALIVE:[tid]::ctag::[tl1_time],[snmp_time];
Related Commands
Retrieve Keep-alive Parameters, on page 84
Parameter Format Description
tl1time 0 | 1 - 60 Sets the TL1 session keep-alive time in minutes. 0
disables the function.
snmptime 0 | 1 - 60 Sets the SNMP session keep-alive time in minutes. 0
disables the function