Chapter 3 ICS Command Reference
ELEVTIME
204 SSU-2000 Technical Reference 12713020-003-2 Revision F.01 – January 2007
ELEVTIME
Use this command to read and set the current time-outs for alarm elevation.
Level 0 Not applicable
Level 1
ELEVTIME [xAy]
If you do not specify a parameter, then all elevation times for each
module within the unit are displayed.
Level 2 Same as Level 1 operation.
Level 3 Same as Level 2 operation, with the following additions:
ELEVTIME [xAy] time
Supervisor-level users can use this command to read and set the current
time-out length for alarm elevation. The unit is required to elevate
MINOR and MAJOR alarms to the next level after a user-settable time
period. Time is in seconds and can be from 60 seconds (1 minute) to 500
000 seconds. If set to 0, alarm elevation is disabled.
Level 4 Same as Level 3 operation
Remarks The default value for the elevation time is 86,400 seconds (24 hours).
Related ALARM, SETUP
RestrictionsNone
Example
The following is an example of the ELEVTIME command message format:
SSU_2000->ELEVTIME
SSU_2000->elevtime
2003-06-18T20:44:50Z ID: SSU2000 Name: SSU_2000
1A01 elevation time is 86400 seconds
1A02 elevation time is 86400 seconds
1A03 elevation time is 86400 seconds
1A04 elevation time is 86400 seconds
1A05 elevation time is 86400 seconds
1A08 elevation time is 86400 seconds
1A09 elevation time is 86400 seconds

Table of Contents

Other manuals for Symmetricom SSU-2000

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Symmetricom SSU-2000 and is the answer not in the manual?

Symmetricom SSU-2000 Specifications

General IconGeneral
BrandSymmetricom
ModelSSU-2000
CategoryPower Supply
LanguageEnglish

Related product manuals