Chapter 2 TL1 Reference
Set Frequency Alarm Threshold Parameters
148 SSU-2000 Technical Reference 12713020-003-2 Revision F.01 – January 2007
Set Frequency Alarm Threshold Parameters
This command sets the input Frequency alarm thresholds for the specified Input
module or port.
Syntax
SET-PRMTR-FREQ:[tid]:[aid]:ctag::[fae],[fac],[fbe],[fbc],[fatau],
[fbtau];
Empty fields leave parameters unchanged.
Related Commands
Retrieve Frequency Parameters, on page 65
Parameter Format Description
aid S1Ay[-z] Sets the parameters for the specfied Input module [or
port].
fae up to
10 000 000
ps/s
Sets the error threshold for input versus A clock.
fac up to
10 000 000
ps/s
Sets the clear threshold for input versus Clock A.
fbe up to
10 000 000
ps/s
Sets the error threshold for input versus B clock.
fbc up to
10 000 000
ps/s
Sets the clear threshold for input versus Clock B, for the
designated input.
fatau 10 - 1000 Sets the frequency error tau, the period (in seconds) for
the frequency to be calculated for input versus A clock.
fbtau 10 - 1000 Sets the frequency error tau, the period (in seconds) for
the frequency to be calculated for input versus B clock.

Table of Contents

Other manuals for Symmetricom SSU-2000

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Symmetricom SSU-2000 and is the answer not in the manual?

Symmetricom SSU-2000 Specifications

General IconGeneral
BrandSymmetricom
ModelSSU-2000
CategoryPower Supply
LanguageEnglish

Related product manuals