12713020-003-2 Revision F.01 – January 2007 SSU-2000 Technical Reference 231
Chapter 3 ICS Command Reference
OUTPUT
OUTPUT xAy FLTMODE {ON|OFF|AUTO}
OUTPUT xAy-z[&&z] {SQUELCH {{0–16}|DISABLE}
OUTPUT xAy-z[&&z] FREQUENCY {8...4096} in 8 kHz steps
OUTPUT xAy SINE {1.544MHZ|6.312MHZ}
OUTPUT xAy 400HZ {ON|OFF}
OUTPUT xAy PLQ {0|{1-16}}
Options are:
ESF|D4 Sets the T1 framing mode: ESF or D4. For DS1 Output
module.
CCS|CAS Sets the E1 framing mode: CCS or CAS. For E1 Output
module.
E1|2048 Sets the signal type for the E1/2048 kHz Output module.
ENABLE|DISABLE
Enable or disable the specified output ports. If the module
is one of a redundant pair, this command only affects the
specified module’s ports.
LEVEL {ACQ|LOCK}
Sets the minimum clock level to ACQUIRE or LOCK mode.
The Output module turns off the output port if the level is
below the minimum clock level.
BYPASS {ON|OFF}
Enables or disables the bypass mode to support Clock C.
133FT|266FT|399FT|533FT|655FT
Sets the line-length parameters for the output line driver.
For DS1 Output module.
CRC {ON|OFF} Enables or disables the CRC setting. For E1 and E1/2048
kHz Output modules.
ZS {ON|OFF} Enables or disables the zero suppression setting. For the
DS1, E1, and E1/2048 kHz Output modules.
SSM {ON|OFF}Enables or disables the SSM setting. For E1 and E1/2048
kHz Output modules.
SSM {4|5|6|7|8}
Sets the E1 SSM bit position. For E1 and E1/2048 kHz
Output modules.
DUTYCYCLE Sets the Composite Clock output to 63/37 or 50/50 duty
cycles. For CC Output module.
COMPENSATE Sets current line compensation for the Composite Clock
output. For CC Output module.
FLTMODE Allows the user to turn the output on or off when the output
level exceeds 2.1v threshold. For 2048 kHz and RS-422
Output modules.