•
Ng Seq impedance Fw
can be set to 50% of the Z
1
tot magnitude of the line 1
which equals in primary ohms 60.4/2 = 30.2.
•
Ng Seq impedance Rv
can be set to 50% of the Z
1
tot magnitude of the line 2.
Setting is for reverse fault in parallel line and therefore magnitude is negative.
Thus setting value is in primary ohms -60.4/2 = -30.2.
• If
Characteristic angle
mode is set to “Fixed”, then the value for
Characteristic
angle
setting can be calculated as below.
Characteristic angle = arctan(X/R)
= arctan(60.1/12.6)
= 78.3 deg
(Equation 280)
The setting
Restrain factor
is set based on the minimum unbalance loading allowed
in the power system network. In this case 10% unbalance is allowed in the given
example system, hence the
Restrain factor
is set to 0.1.
Fault simulation
The phase to ground faults are simulated in the given example shown in
Figure 580
,
the relay is located at the sending end of the line1 and the output is captured for
forward and reverse direction fault.
The phase A to ground fault is applied on the line1 in the forward direction, the Z
2
value is positive as well as exceeds the
Ng seq impedance Fw
setting threshold,
hence the START output issued, FAULT_DIR indicates the fault in the forward
direction and the OPERATE output will be issued after the
Operate delay time
setting has passed as shown in below
Figure 581
.
Figure 581: Phase A to ground fault on forward direction
The phase A to ground fault is applied on the line2 in the reverse direction, the
calculated Z
2
value is negative as well as lower the
Ng seq impedance Rv
setting
threshold, hence the START output issued, FAULT_DIR indicates the fault in the
reverse direction and the OPERATE output will be issued after the
Operate delay
time
setting has passed as shown in below
Figure 582
.
1MRS759142 F
Protection functions
REX640
Technical Manual
1043