9.4.6.4 ESSXSWI Output signals
Table 1495: ESSXSWI Output signals
Name Type Description
OPENPOS BOOLEAN Apparatus open position
CLOSEPOS BOOLEAN Apparatus closed position
OKPOS BOOLEAN Apparatus position is ok
9.4.7 Settings
9.4.7.1 DCSXSWI Settings
Table 1496: DCSXSWI Non group settings (Basic)
Parameter Values (Range) Unit Step Default Description
Identification DCSXSWI1 switch
position
Control Object
identification
Table 1497: DCSXSWI Non group settings (Advanced)
Parameter Values (Range) Unit Step Default Description
Event delay 0...60000 ms 1 30000 Event delay of the
intermediate and
faulty position
Vendor 0 External equipment
vendor
Serial number 0 External equipment
serial number
Model 0 External equipment
model
9.4.7.2 ESSXSWI Settings
Table 1498: ESSXSWI Non group settings (Basic)
Parameter Values (Range) Unit Step Default Description
Identification ESSXSWI1 switch
position
Control Object
identification
Table 1499: ESSXSWI Non group settings (Advanced)
Parameter Values (Range) Unit Step Default Description
Event delay 0...60000 ms 1 30000 Event delay of the
intermediate and
faulty position
Vendor 0 External equipment
vendor
Serial number 0 External equipment
serial number
Model 0 External equipment
model
Control functions 1MRS759142 F
1542 REX640