Table 588: HAEFPTOC Group settings (Advanced)
Parameter Values (Range) Unit Step Default Description
Minimum operate
time
100...200000 ms 10 500 Minimum operate
time for IDMT
curves
Type of reset curve
1=Immediate
2=Def time reset
3=Inverse reset
1=Immediate Selection of reset
curve type
Enable reference
use
0=False
1=True
0=False Enable using cur-
rent reference from
other IEDs instead
of stand-alone
Table 589: HAEFPTOC Non group settings (Basic)
Parameter Values (Range) Unit Step Default Description
Operation
1=on
5=off
1=on Operation Off / On
Curve parameter A 0.0086...120.0000 0.0001 28.2000 Parameter A for
customer program-
mable curve
Curve parameter B 0.0000...0.7120 0.0001 0.1217 Parameter B for
customer program-
mable curve
Curve parameter C 0.02...2.00 0.01 2.00 Parameter C for
customer program-
mable curve
Curve parameter D 0.46...30.00 0.01 29.10 Parameter D for
customer program-
mable curve
Curve parameter E 0.0...1.0 0.1 1.0 Parameter E for
customer program-
mable curve
Table 590: HAEFPTOC Non group settings (Advanced)
Parameter
Values (Range) Unit Step Default Description
Reset delay time 0...60000 ms 10 20 Reset delay time
4.2.6.9 HAEFPTOC Monitored data
Table 591: HAEFPTOC Monitored data
Name
Type Values (Range) Unit Description
START_DUR FLOAT32 0.00...100.00 % Ratio of start time / op-
erate time
I_HARM_RES FLOAT32 0.0...30000.0 A Calculated harmonics
current
BLKD_I_REF BOOLEAN
0=False
1=True
Current comparison
status indicator
HAEFPTOC Enum
1=on
2=blocked
3=test
4=test/blocked
5=off
Status
Protection functions 1MRS759142 F
528 REX640
Technical Manual