ABB RELION REX640 - Synchronization control

ABB RELION REX640
1960 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
The monitored data CB_CL_BLKD depends on the inputs GCB_TEST and EXT_CHECK,
and also on IED test mode as described in
Table 1518
. CB_CL_BLKD is available in the
Monitored data view.
Table 1518: Monitored data CB_CL_BLKD activation based on the inputs
IED test mode Inputs Monitored data
GCB_TEST EXT_CHECK CB_CL_BLKD
TRUE TRUE TRUE 1 (“Unblocked”)
FALSE FALSE
TRUE TRUE FALSE 2 (“Ext Check Fail”)
FALSE FALSE
TRUE FALSE N/A 3 (“IED Test CB Serv-
ice”)
FALSE TRUE N/A 4 (“IED Service CB
Test”)
The close CB condition is blocked if the CB_CL_BLKD status is 2(“Ext Check Fail”),
3(“IED Test CB Service”) or 4(“IED Service CB Test”).
In case for BYPASS input activation,
If GCB_TEST is activated, CLOSE_CB is activated.
If GCB_TEST is deactivated, and the bus and generator terminal voltages are both
live or one side live, CLOSE_CB is not activated.
Synchronization control
The general bus bar arrangement for a generator bus is shown in
Figure 857
.
The bus to which the generator is connected is determined based on the
circuit breaker and isolator position inputs (GCB_OPEN, GCB_CLOSE, ISO_A_CLOSE
and ISO_B_CLOSE). The generator's bus connection status is shared with the
autosynchronizer co-ordinator function ASCGAPC as part of the GEN_ASC_DATA
output.
Bus A
Gen CB
Bus B
G
Bus A
Gen CB
Single busbar arrangement Double busbar arrangement
ISO A
ISO B
ISO A
G
Figure 857: Different bus bar arrangements for a generator bus
1MRS759142 F
Control functions
REX640
Technical Manual
1565