tuning procedure is also released when the
Controller mode
is switched from
“Manual” to “Automatic”.
PASANCR has an adaptive U
ref
feature. The
V Ref adaptive mode
setting is used
to enable or disable the functionality. The functionality allows slow changes
in measured zero-sequence voltage and therefore reduces unnecessary tuning
operations. If the measured zero-sequence voltage does not exceed the
V Res
change level
setting during the time defined in
V Ref adaptive delay
setting, the
existing measured zero-sequence voltage is stored as a new reference voltage U
ref
at the end of the adaptive period. The operation principle of the adaptive U
ref
feature is explained in
Figure 925
.
hange level
Tuning
delay
Adapve Uref
feature
No unnecessary tuning operaons as the
U
ref
is adjusted e.g. every 10 minutes (V Ref
adapve delay seng)
V Ref adapve
delay
Unnecessary
tuning
Tuning
delay
Figure 925: Example of Uo fluctuation with and without adaptive Uref feature
(amplitude triggering mode)
9.11.6.3 Network parameter calculation
To explain the controller, the simplified equivalent circuit of a three-phase
distribution network illustrated in
Figure 926
is used. The controller assumes that:
• The real network is presented with its shunt admittances neglecting line series
impedances as their values are very small compared with the shunt admittances.
• The individual phase admittances of the network are presented with symmetrical
phase admittances whose sum equals
Y G j Bsymm symm symm= + ⋅
(Equation 386)
(one third connected in each phase)
• The natural asymmetry in a real network is due to differences in individual phase
admittances and it is presented with an asymmetry admittance concentrated
into phase A and presented with admittance
Control functions
1MRS759142 F
1736 REX640
Technical Manual