Table 87: FLTRFRC Non group settings (Basic)
Parameter Values (Range) Unit Step Default Description
Operation
1=on
5=off
1=on Operation Off / On
Trig mode
0=From all faults
1=From operate
2=From only start
0=From all faults Triggering mode
Table 88: FLTRFRC Non group settings (Advanced)
Parameter Values (Range) Unit Step Default Description
A measurement
mode
1=RMS
2=DFT
3=Peak-to-Peak
2=DFT Selects used meas-
urement mode
phase currents and
residual current
3.9.6 Monitored data
3.9.6.1 FLTRFRC Monitored data
Table 89: FLTRFRC Monitored data
Name Type Values (Range) Unit Description
Fault number INT32 0...999999 Fault record number
Time and date Timestamp Fault record time stamp
Protection (rec. set 1) Enum
0=None
1=PHLPTOC1
2=PHLPTOC2
6=PHHPTOC1
7=PHHPTOC2
8=PHHPTOC3
9=PHHPTOC4
12=PHIPTOC1
13=PHIPTOC2
17=EFLPTOC1
18=EFLPTOC2
19=EFLPTOC3
22=EFHPTOC1
23=EFHPTOC2
24=EFHPTOC3
25=EFHPTOC4
30=EFIPTOC1
31=EFIPTOC2
32=EFIPTOC3
35=NSPTOC1
36=NSPTOC2
-7=INTRPTEF1
-5=STTPMSU1
-3=JAMPTOC1
Protection function
(rec. set1)
Table continues on the next page
1MRS759142 F Basic functions
REX640
Technical Manual
147