Name Type Description
H_LO_LEFT BOOLEAN H-bridge output lower left
H_LO_RIGHT BOOLEAN H-bridge output lower right
CTL_ITL_BLKD BOOLEAN Control is blocked due to in-
terlocking
9.2.7 P3SXSWI Settings
Table 1481: P3SXSWI Non group settings (Basic)
Parameter Values (Range) Unit Step Default Description
Operation
1=on
5=off
1=on Operation Off / On
Control mode
1=Direct control
2=With RIO600
SCM
1=Direct control Direct control or
RIO600 SCM con-
trol
Reed contact
0=Not available
1=Available
0=Not available Availability of reed
contact
Select timeout 10000...300000 ms 10000 30000 Select timeout in
ms
Control model
0=status-only
1=direct-with-nor-
mal-security
4=sbo-with-en-
hanced-security
4=sbo-with-en-
hanced-security
Select control mod-
el
Operation timeout
DC
10...60000 ms 1 30000 Timeout for nega-
tive termination for
disconnector
Operation timeout
ES
10...60000 ms 1 30000 Timeout for nega-
tive termination for
earthing switch
Motor braking
0=False
1=True
1=True Motor braking
on/off selection
Identification P3SXSWI1 switch
position
Control object
identification
Table 1482: P3SXSWI Non group settings (Advanced)
Parameter
Values (Range) Unit Step Default Description
Operation counter
DC
0...10000 1 0 Disconnector oper-
ation cycles
Operation counter
ES
0...10000 1 0 Earthing switch op-
eration cycles
Event delay 0...60000 ms 1 10000 Event delay of in-
termediate or faul-
ty position
Motor start time-
out
0...32000 ms 100 0 Timeout for motor
to start
Motor brake time 10...500 ms 1 100 Motor brake time
Interlocking Pls Len 1...10 s 1 2 Pulse length for in-
terlocking violation
signal
Vendor 0 External equipment
vendor
Table continues on the next page