Improper analog channel configuration causes a validation error if the analog
channels are not completely configured or they do not match with certain settings.
For troubleshooting, check the contents of this chapter and also the preprocessing
blocks in this document. The configuration can be written to the protection relay
once the mismatch is corrected.
8.1.7.5 Signals
VMMXU Input signals
Table 1387: VMMXU Input signals
Name Type Default Description
U3P SIGNAL - Three-phase voltages
BLOCK BOOLEAN 0=False Block signal for all bi-
nary outputs
VMMXU Output signals
Table 1388: VMMXU Output signals
Name Type Description
HIGH_ALARM BOOLEAN High alarm
HIGH_WARN BOOLEAN High warning
LOW_WARN BOOLEAN Low warning
LOW_ALARM BOOLEAN Low alarm
U_INST_AB FLOAT32 Phase AB voltage instantane-
ous value amplitude in kV
U_INST_BC FLOAT32 Phase BC voltage instantane-
ous value amplitude in kV
U_INST_CA FLOAT32 Phase CA voltage instantane-
ous value amplitude in kV
U_INST_A FLOAT32 Phase A voltage instantane-
ous value amplitude in kV
U_INST_B FLOAT32 Phase B voltage instantane-
ous value amplitude in kV
U_INST_C FLOAT32 Phase C voltage instantane-
ous value amplitude in kV
U_DMD_AB FLOAT32 Demand value of U12 voltage
U_DMD_BC FLOAT32 Demand value of U23 voltage
U_DMD_CA FLOAT32 Demand value of U31 voltage
U_DMD_A FLOAT32 Demand value of UL1 voltage
U_DMD_B FLOAT32 Demand value of UL2 voltage
U_DMD_C FLOAT32 Demand value of UL3 voltage