ABB RELION REX640 - 7.3.7.2 HSARSPTR Output signals; 7.3.8 HSARSPTR Settings

ABB RELION REX640
1960 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Name Type Default Description
BLOCK BOOLEAN 0=False Block signal for acti-
vating the blocking
mode
RESET BOOLEAN 0=False Reset loss of life cal-
culation
RST_AVGAGING BOOLEAN 0=False Reset average ageing
rate calculation
7.3.7.2 HSARSPTR Output signals
Table 1326: HSARSPTR Output signals
Name Type Description
ALARM BOOLEAN Alarm signal
WARNING BOOLEAN Warning signal
ALM_AGE_RATE BOOLEAN Alarm signal for Avg ageing
rate over set time period
TOPOIL_TEMP FLOAT32 Calculated value of top oil
temperature
HOTSPOT_TEMP FLOAT32 Calculated value of hot spot
temperature
7.3.8 HSARSPTR Settings
Table 1327: HSARSPTR Group settings (Basic)
Parameter Values (Range) Unit Step Default Description
Cooling mode
1=ONAN
2=ONAF
3=OFAF
4=ODAF
1=ONAN Transformer cool-
ing method
Alarm level 50.0...350.0 °C 0.1 120.0 Alarm level for hot-
spot temperature
Warning level 50.0...350.0 °C 0.1 100.0 Warning level for
hotspot tempera-
ture
Alarm delay time 0...3600000 ms 10 10000 Time delay for hot-
spot temperature
alarm
Warning delay time 0...3600000 ms 10 10000 Time delay for hot-
spot temperature
warning
Average ambient
Tmp
-20.00...70.00 °C 0.01 20.00 Average ambient
temperature
Table 1328: HSARSPTR Non group settings (Basic)
Parameter Values (Range) Unit Step Default Description
Operation
1=on
1=on Operation Off / On
Table continues on the next page
1MRS759142 F Condition monitoring functions
REX640
Technical Manual
1395