different days of the week. For example, if the signal should be active on Mondays
between 7:15 and 16:00, the
Monday Act enable
setting should be "True",
Monday
Act hour
should be "7",
Monday Act Mn
should be "15", and
Monday off delay
should
be "525" minutes. The behavior of output Q is illustrated in
Figure 130
.
Monday
Q
06:0003:00
12:0009:00 18:0015:00
00:0021:00
SetMondayActhour=07hrs
SetMondayActMn=15min
SetMondayoffdelay=525min
Figure 130: Example setting values for output Q activation
3.20.3.6 Signals
DTMGAPC Input signals
Table 211: DTMGAPC Input signals
Name Type Default Description
BLOCK BOOLEAN 0=False Block signal for bina-
ry output
FREEZE BOOLEAN 0=False Freeze signal for bina-
ry output
DTMGAPC Output signals
Table 212: DTMGAPC Output signals
Name Type Description
Q BOOLEAN Output status
3.20.3.7 DTMGAPC Settings
Table 213: DTMGAPC Non group settings (Basic)
Parameter Values (Range) Unit Step Default Description
Operation
1=on
5=off
1=on Operation Off / On
Monday Act enable
0=False
1=True
false Activation / deacti-
vation need on
Monday
Monday Act hour 0...23 h 8 Activation hour
time for Monday
Table continues on the next page