3.25.2.4 Settings
Table 352: SCHLCCH Settings
Parameter
1
Values (Range) Unit Step Default Description
Port n Mode
Off
On
Dedicated channel
2
On
Mode selection for rear port(s). If
port is not used, it can be set to
“Off”. Port cannot be set to “Off
when
Redundant mode
is “HSR”
or “PRP” and port is one of the
redundant ports (LAN A or LAN
B).
Filter Mode Xn
Off
SMV
GOOSE
GOOSE & SMV
Off
Selection for message filtering
Goose rate limiter Xn 0.512...90.000 10.000 Goose rate limit (Mbps)
SMV rate limit Xn 0.512...90.000 70.000 Sampled measured values rate
limit (Mbps)
Def. rate limit Xn 0.512...90.000 8.000 Default rate limit (Mbps)
3.25.2.5 Monitored data
Monitored data is available in six locations.
Monitoring> Communication> Ethernet> Activity> CH1LIV
Monitoring> Communication> Ethernet> Activity> CH2LIV
Monitoring/> Communication> Ethernet> Activity> CH3LIV
Monitoring/> Communication> Ethernet> Link statuses> LNK1LIV
Monitoring> Communication> Ethernet> Link statuses> LNK2LIV
Monitoring> Communication> Ethernet> Link statuses> LNK3LIV
3.25.2.6 Diagnostics
Diagnostics data is available in Monitoring> Communication> Ethernet>
Diagnostics> Xn (n = 1...3).
Table 353: Diagnostic parameters for X1/LAN, X2/LAN and X3/LAN
Parameter Values (Range) Unit Step Default Description
Reset counters FALSE / TRUE FALSE Reset counters command
GOOSE limit count 0...1000000 0 Goose rate limit exceed count
SMV limit count 0...1000000 0 Sampled measured values limit
exceed count
Ucast limit count 0...1000000 0 Unicast rate limit exceed count
Def. limit count 0...1000000 0 Default rate limit exceed count
GOOSE limit alarm FALSE / TRUE FALSE Goose rate limit exceed alarm
SMV limit alarm FALSE / TRUE FALSE Sampled measured values limit
alarm
Ucast limit alarm FALSE / TRUE FALSE Unicast rate limit exceed alarm
Def. limit alarm FALSE / TRUE FALSE Default rate limit exceed alarm