ABB RELION REX640 - 9.6.7.2 ASGCSYN Output signals

ABB RELION REX640
1960 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Name Type Default Description
MODE_GOV Enum 1=Droop Governor working
mode
MODE_AVR Enum 9=Droop AVR working mode
DROOP_GOV BOOLEAN 0=False Governor droop mode
status
DROOP_AVR BOOLEAN 0=False AVR droop mode sta-
tus
GOV_ALM_HI BOOLEAN 0=False Governor alarm due
to high limits
GOV_ALM_LO BOOLEAN 0=False Governor alarm due
to low limits
AVR_ALM_HI BOOLEAN 0=False AVR alarm due to high
limits
AVR_ALM_LO BOOLEAN 0=False AVR alarm due to low
limits
DIFF_U_ASC1 FLOAT32 0.00 Network breaker volt-
age difference from
ASCGAPC1
DIFF_F_ASC1 FLOAT32 0.000 Network breaker fre-
quency difference
from ASCGAPC1
ASC1_GEN_DAT INT32 0 Integer weighted in-
put data from ASC-
GAPC1
9.6.7.2 ASGCSYN Output signals
Table 1520: ASGCSYN Output signals
Name Type Description
SYNC_INPRO BOOLEAN Auto synchronization in pro-
gress
SYNC_OK BOOLEAN Systems in synchronism
MATCH_INPRO BOOLEAN Voltage and frequency
matching in progress
MATCH_OK BOOLEAN Voltage and frequency of the
systems matched
CLOSE_CB BOOLEAN CB close signal
CL_FAIL_AL BOOLEAN CB closing failed
CMD_FAIL_AL BOOLEAN CB closing request failed
LBDG BOOLEAN Live bus, dead generator
LBLG BOOLEAN Live bus, live generator
DBLG BOOLEAN Dead bus, live generator
Table continues on the next page
1MRS759142 F Control functions
REX640
Technical Manual
1581