EasyManua.ls Logo

ABB RELION REX640 - 4.12.5.8 Signals; CNUPTOV Input signals

ABB RELION REX640
1960 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
U k U U U kA B C N+ +
( )
= +
( )
1 2
Figure 651: Equation
If the system is symmetrical, that is, the system is healthy without any fault
U U UA B C+ + = 0
Figure 652: Equation
Combining
Figure 651
and
Figure 652
results in
U k U U kA A N+
( )
= +
( )
1 2
Figure 653: Equation
U U
k
k
N A=
( )
+
( )
1
1 2
Figure 654: Equation
Considering the neutral VT ratio, per unit voltage referred to the neutral side is
given by
U
U
k
k
U
N
A
N pr
=
( )
+
( )
1
1 2
_
Figure 655: Equation
For example, if the impedance of the 20 kV system (U
A
= 11.547 kV) capacitance
drops by 5 percent, that is, k = 0.95, the neutral voltage is around 200 V according
to
Figure 654
. If the voltage rating of a neutral VT is 20 kV/100 V, then in per unit
terms refer to neutral side, the neutral voltage is around 0.01 · Un, that is,
Start value
should be set around 0.01.
In addition, assume that residual voltage (terminal side) is measured directly using
an open-delta VT having ratio of
20
3
100
3
100
3
kV V V
/ /
. Also, the
Primary voltage
and
Secondary voltage
settings under Configuration> Analog inputs> Voltage
(UoB,VT) in a grounded system are set as 11.547 kV and 100 V, respectively. Similarly,
if the VT connected at the neutral point has a ratio of
20
3
100
3
kV V
/
, the
Primary
voltage
and
Secondary voltage
settings under Configuration> Analog inputs>
Voltage (UoB,VT) must be set as 20 kV and 100 V, respectively.
4.12.5.8 Signals
Protection functions
1MRS759142 F
1154 REX640
Technical Manual

Table of Contents

Other manuals for ABB RELION REX640

Related product manuals