Table 1191: RESCPSCH Input signals
Name Type Default Description
BLOCK BOOLEAN 0=False Block signal for acti-
vating the blocking
mode
BLK_CS_OPR BOOLEAN 0=False Signal for blocking
CS and OPR in all
schemes
CSBLK BOOLEAN 0=False Reverse residual over-
current signal for Car-
rier Send
CACC BOOLEAN 0=False Signal to be used for
tripping by Communi-
cation Scheme
CSOR BOOLEAN 0=False Overreaching residual
overcurrent signal for
Carrier Send
CSUR BOOLEAN 0=False Underreaching resid-
ual overcurrent signal
for Carrier Send
CR_PRM BOOLEAN 0=False Received teleprotec-
tion permissive from
the other side
CR_BLOCKING BOOLEAN 0=False Received teleprotec-
tion blocking from
the other side
CR_INTER_TR BOOLEAN 0=False Received direct trip
from the other side
CRG BOOLEAN 0=False Carrier guard signal
received
5.11.6.2 RESCPSCH Output signals
Table 1192: RESCPSCH Output signals
Name Type Description
OPERATE BOOLEAN Operate
CS_PRM BOOLEAN Permissive transmitted to the
other side
CS_BLOCKING BOOLEAN Blocking transmitted to the
other side
CS_INTER_TR BOOLEAN Direct trip transmitted to the
other side
Table continues on the next page