6.3.8.4 HZCCASPVC Output signals
Table 1257: HZCCASPVC Output signals
Name Type Description
ALARM BOOLEAN Alarm output
6.3.8.5 HZCCBSPVC Output signals
Table 1258: HZCCBSPVC Output signals
Name Type Description
ALARM BOOLEAN Alarm output
6.3.8.6 HZCCCSPVC Output signals
Table 1259: HZCCCSPVC Output signals
Name Type Description
ALARM BOOLEAN Alarm output
6.3.9 Settings
6.3.9.1 HZCCASPVC Settings
Table 1260: HZCCASPVC Non group settings (Basic)
Parameter Values (Range) Unit Step Default Description
Operation
1=on
5=off
1=on Operation Off / On
Start value 1.0...100.0 %In 0.1 10.0 Start value, per-
centage of the
nominal current
Alarm delay time 100...300000 ms 10 3000 Alarm delay time
Alarm output mode
1=Non-latched
3=Lockout
3=Lockout Select the opera-
tion mode for
alarm output
Table 1261: HZCCASPVC Non group settings (Advanced)
Parameter Values (Range) Unit Step Default Description
Reset delay time 0...60000 ms 10 20 Reset delay time
Measurement
mode
2=DFT
3=Peak-to-Peak
2=DFT Selects used meas-
urement mode
6.3.9.2 HZCCBSPVC Settings
Supervision functions 1MRS759142 F
1324 REX640
Technical Manual