Parameter Values (Range) Unit Step Default Description
2=Variable Pulse
3=Variable Interval
Auto Syn mode
-1=Semi-automatic
synchronising
mode
1=Automatic syn-
chronising mode
3=Manual mode
3=Manual mode Auto synchroniza-
tion operation
mode
Table 1524: ASGCSYN Non group settings (Advanced)
Parameter Values (Range) Unit Step Default Description
Minimum Syn time 0...60000 ms 10 0 Minimum time to
accept synchroniz-
ing
Maximum Syn time 100...6000000 ms 10 60000 Maximum time to
accept synchroniz-
ing
Energizing time 100...60000 ms 10 100 Time delay for en-
ergizing check
Central PMS
present
1=No
2=Yes
1=No Centralized Power
Management Sys-
tem present
Volt pulse off Intv 1000...20000 ms 10 2000 Set voltage pulse
off interval time
Volt pulse Min Dur 50...2000 ms 10 50 Set voltage pulse
minimum duration
Freq pulse off Intv 1000...120000 ms 10 20000 Set frequency pulse
off interval time
Freq pulse Min Dur 50...2000 ms 10 50 Set frequency pulse
minimum duration
9.6.9 ASGCSYN Monitored data
Table 1525: ASGCSYN Monitored data
Name Type Values (Range) Unit Description
ENERG_STATE Enum
0=Unknown
1=Both Live
2=Live G, Dead B
3=Dead G, Live B
4=Both Dead
Energization state of
bus and generator
U_DIFF_MEAS FLOAT32 -3.00...3.00 xUn Calculated voltage am-
plitude difference
FR_DIFF_MEAS FLOAT32 -1.500...1.500 xFn Calculated voltage fre-
quency difference
PH_DIFF_MEAS FLOAT32 -180.00...180.00 deg Calculated voltage
phase angle difference
U_BUS_MEAS FLOAT32 0.00...5.00 xUn Calculated bus voltage
amplitude
U_GEN_MEAS FLOAT32 0.00...5.00 xUn Calculated generator
voltage amplitude
FR_BUS_MEAS FLOAT32 35.00...75.00 Hz Calculated bus frequen-
cy
FR_GEN_MEAS FLOAT32 35.00...75.00 Hz Calculated generator
frequency
Table continues on the next page
Control functions 1MRS759142 F
1584 REX640
Technical Manual