4.1.12.8 GSLPTOC Settings
Table 498: GSLPTOC Group settings (Basic)
Parameter Values (Range) Unit Step Default Description
Sel operate har-
monic
1=Fundamental
3=Third harmonic
5=Fifth harmonic
1=Fundamental Select operating
harmonic
Alarm start value 0.10...10.00 A 0.01 0.25 Alarm start value
Operate start value 0.10...10.00 A 0.01 0.50 Operate start value
Alarm delay time 40...30000 ms 10 3000 Alarm delay time
Operate delay time 40...30000 ms 10 3000 Operate delay time
Table 499: GSLPTOC Non group settings (Basic)
Parameter Values (Range) Unit Step Default Description
Operation
1=on
5=off
1=on Operation Off / On
Reset delay time 0...10000 ms 1 1000 Reset delay time
4.1.12.9 GSLPTOC Monitored data
Table 500: GSLPTOC Monitored data
Name
Type Values (Range) Unit Description
I_SHAFT FLOAT32 0.00...10.00 A Amplitude of the meas-
ured shaft current
I_SHAFT_H1 FLOAT32 0.00...10.00 A Amplitude of the funda-
mental component of
the measured shaft cur-
rent
I_SHAFT_H3 FLOAT32 0.00...10.00 A Amplitude of the third
harmonic component
of the measured shaft
current
I_SHAFT_H5 FLOAT32 0.00...10.00 A Amplitude of the fifth
harmonic component
of the measured shaft
current
START_DUR FLOAT32 0.00...100.00 % Ratio of start time / op-
erate time
GSLPTOC Enum
1=on
2=blocked
3=test
4=test/blocked
5=off
Status
1MRS759142 F Protection functions
REX640
Technical Manual
439