3.19.1.2 Functionality
The good signal quality function QTY_GOOD evaluates the quality bits of the input
signal and passes it as a Boolean signal for the application.
The IN input can be connected to any logic application signal (except preprocessing
block). Due to application logic quality bit propagation, each (simple and even
combined) signal has quality which can be evaluated.
The OUT output indicates quality good of the input signal. Input signals that have no
quality bits set or only test bit is set, will indicate quality good status.
3.19.1.3 Signals
Table 155: QTY_GOOD Input signals
Name Type Default Description
IN Any 0 Input signal
Table 156: QTY_GOOD Output signals
Name Type Description
OUT BOOLEAN Output signal
3.19.2 Bad signal quality QTY_BAD
3.19.2.1 Function block
Figure 103: Function block
3.19.2.2 Functionality
The bad signal quality function QTY_BAD evaluates the quality bits of the input
signal and passes it as a Boolean signal for the application.
The IN input can be connected to any logic application signal (except preprocessing
block). Due to application logic quality bit propagation, each (simple and even
combined) signal has quality which can be evaluated.
The OUT output indicates quality bad of the input signal. Input signals that have any
other than test bit set, will indicate quality bad status.
Basic functions
1MRS759142 F
214 REX640
Technical Manual