Activation of OPERATE output results to automatic triggering of fault
recording.
The recording function of IFPTOC includes recorded data 1 data objects as shown in
Table 636
.
Table 636: Recorded data 1 data objects of the IFPTOC function
Parameter name Parameter description Recorded Data DO
Triggering time
Triggering time (Timestamp) IF1RFRCx.TchV.t.
Residual voltage
Residual voltage magnitude [xUn] (MX) IF1RFRCx.VRes.mag.f
Residual current
Residual current magnitude [xIn] (MX) IF1RFRCx.ARes.mag.f
Touch voltage
Touch voltage magnitude [V] (MX) IF1RFRCx.TchV.mag.f
Touch voltage rms
Touch voltage magnitude incl harmonics [V] (MX) IF1RFRCxTchVRms.mag.f
Fault current
Fault current magnitude (incl. reduction) [A] (MX)) IF1RFRCx.FltA.res.cVal.mag.f
Fault current rms
Fault current magnitude incl harmonics (and reduc-
tion) [A]
(MX) IF1RFRCx.FltARms.mag.f
Start duration
Start duration [%] (MX) IF1RFRCx.StrDur.mag.f
Faulted phase
Faulted phase (ST) IF1RFRCx.FltLoop.stVal
Fault resistance
Fault point resistance [in primary ohm] (MX) IF1RFRCx.FltPtRis.mag.f
Transient Ris Comp
Transient resistive component [A] (MX) IF1RFRCx.AResReal.mag.f
Transient React Comp
Transient reactive component [A] (MX) IF1RFRCx.AResImag.mag.f
Non qualified Harmon
Non qualified harmonics (ST) IF1RFRCx.NonQualH.stVal
EF indication
Non-directional earth fault detection (ST) IF1RFRCx.EFDet.stVal
Valid EF detection
Valid EF detection in protected feeder (ST) IF1RFRCx.EFDetVald.stVal
XC fault detection
Cross-country fault detection (ST) IF1RFRCx.XcnDet.stVal
Time left to operate
Time left to operate [sec.] (MX) IF1RFRCx.TmOpEst.mag.f
Intermittent EF Det
Restriking (intermittent) earth fault detection (ST) IF1RFRCx.ItmEFInd.stVal
Started timers
Started timers (ST) IF1RFRCx.ActStrSt.stVal
Operated timers
Operated timers (ST) IF1RFRCx.ActOpSt.stVal
Operate time
Actual operate time [sec] (MX) IF1RFRCx.StrOpTm.mag.f
A total of two sets of recorded data are saved in data banks
Recorded data 1
and
Recorded data 2
. Data bank
Recorded data 1
holds the most recent recorded data
and the older data is moved into the data bank
Recorded data 2
when triggering
occurs. When all two banks have data and a new triggering occurs, the latest
data is placed into bank
Recorded data 1
and the data in bank
Recorded data 2
is overwritten by the data from bank
Recorded data 1
.
It is possible to reset corresponding recorded data by either:
activating LHMI parameter Clear/Clear/IFPTOCx reset = 1 (“Clear”) or
writing directly by MMS LD0.IFPTRCx.RcdRs.Oper.ctlVal = 1 (“Clear”)”