Name Type Description
GRPOFF Group signal Group off signal for function blocks
DEV_WARN BOOLEAN Protection relay internal warning
FRQ_ADP_WARN BOOLEAN Frequency adaptivity warning
FRQ_ADP_FAIL BOOLEAN Frequency adaptivity status fail
FRQ_ADP_BU BOOLEAN Main frequency adaptivity source
3.7.4 Settings
Table 69: PROTECTION Settings
Parameter Values (Range) Unit Step Default Description
SG operation mode
1=Operator
2=Logic mode 1
3=Logic mode 2
1=Operator
Operation mode for setting
group change
3.8 Local/Remote control CONTROL
3.8.1 Function block
Figure 50: Function block
3.8.2 Functionality
Local/Remote control is by default realized through the R/L button on the front
panel. The control via binary input can be enabled by setting the value of the
LR control
setting to "Binary input". The binary input control requires that the
CONTROL function is instantiated in the product configuration.
Local/Remote control supports multilevel access for control operations in
substations according to the IEC 61850 standard. Multilevel control access with
separate station control access level is not supported by other protocols than IEC
61850.
The actual Local/Remote control state is evaluated by the priority scheme on the
function block inputs. If more than one input is active, the input with the highest
priority is selected. The priority order is “off”, “local”, “station”, “remote”, “all”.
1MRS759142 F
Basic functions
REX640
Technical Manual
135