Table 11: Non group settings
Parameter Values (Range) Unit Step Default Description
IP address 192.168.0.254 IP address for front
port (fixed)
Mac address XX-XX-XX-XX-XX-XX Mac address for
front port
3.1.6 System settings
Table 12: Non group settings
Parameter Values (Range) Unit Step Default Description
Rated frequency
1=50Hz
2=60Hz
1=50Hz Rated frequency of
the network
Phase rotation
1=ABC
2=ACB
1=ABC Phase rotation or-
der
Blocking mode
1=Freeze timer
2=Block all
3=Block OPERATE
output
1=Freeze timer Behaviour for func-
tion BLOCK inputs
Bay name REX640 Bay name in system
IDMT Sat point 10...50 I/I> 1 50 Overcurrent IDMT
saturation point
Frequency adaptivi-
ty
0=Disable
1=Enable
0=Disable Enabling frequency
adaptivity
SMV Max Delay
0=2/2 ms
1=3/3 ms
2=5/4 ms
3=6/5 ms
4=7/6 ms
1=3/3 ms SMV Maximum al-
lowed delay
Test mode selec-
tion
1=Local
2=Local+Remote,
maintenance
3=Local+Remote,
all levels
4=Binary input
1=Local Authority for re-
mote activation of
test mode
3.1.7 HMI Settings
1MRS759142 F Basic functions
REX640
Technical Manual
59