ABB RELION REX640 - 4.1.2.13 Technical revision history

ABB RELION REX640
1960 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Characteristic Value
Phase angle: ±2°
DPHHPDOC
Current:
±1.5% of the set value or ±0.002 × I
n
(at currents in the range of 0.1…10 × I
n
)
±5.0% of the set value
(at currents in the range of 10…40 × I
n
)
Voltage:
±1.5% of the set value or ±0.002 × U
n
Phase angle: ±2°
Start time
1, 2
I
Fault
= 2.0 x set
Start value
Minimum Typical Maximum
39 ms 43 ms 47 ms
Reset time Typically 40 ms
Reset ratio Typically 0.96
Retardation time <35 ms
Operate time accu-
racy in definite time
mode
±1.0% of the set value or ±20 ms
Operate time accu-
racy in inverse time
mode
±5.0% of the theoretical value or ±20 ms
3
Suppression of har-
monics
DFT: -50 dB at f = n × f
n
, where n = 2, 3, 4, 5,…
4.1.2.13 Technical revision history
Table 413: DPHLPDOC Technical revision history
Product
connectivi
ty level
Technical
revision
Change
PCL4 G Setting
Start value
maximum value extended to 10.00xIn.
1
Measurement mode
and
Pol quantity
= default, current before fault = 0.0 × I
n
, voltage before fault
= 1.0 × U
n
, f
n
= 50 Hz, fault current in one phase with nominal frequency injected from random
phase angle, results based on statistical distribution of 1000 measurements
2
Includes the delay of the signal output contact
3
Maximum
Start value
= 2.5 × I
n
,
Start value
multiples in range of 1.5...20
Protection functions 1MRS759142 F
368 REX640
Technical Manual