Table 1050: MAPGAPC Non group settings (Advanced)
Parameter Values (Range) Unit Step Default Description
Reset delay time 0...60000 ms 100 0 Reset delay time
Absolute hysteresis 0.01...100.00 0.01 0.10 Absolute hysteresis
for operation
4.11.8 MAPGAPC Monitored data
Table 1051: MAPGAPC Monitored data
Name Type Values (Range) Unit Description
START_DUR FLOAT32 0.00...100.00 % Ratio of start time / op-
erate time
MAPGAPC Enum
1=on
2=blocked
3=test
4=test/blocked
5=off
Status
4.11.9 Technical data
Table 1052: MAPGAPC Technical data
Characteristic Value
Operation accuracy
±1.0 % of the set value or ±20 ms
4.12 Capacitor bank protection
4.12.1 Three-phase overload protection for shunt capacitor
banks COLPTOC (ANSI 51,37,86C)
4.12.1.1 Identification
Function description IEC 61850
identification
IEC 60617
identification
ANSI/IEEE C37.2
device number
Three-phase overload protection
for shunt capacitor banks
COLPTOC 3I> 3I< 51,37,86C
1MRS759142 F Protection functions
REX640
Technical Manual
1109

Table of Contents

Other manuals for ABB RELION REX640