The temperature protection using the RTD sensors can be done using the function
block. The measured temperature can be fed from the RTD sensor to the function
input that detects too high temperatures in the motor bearings or windings, for
example. When the ENA_ADD input is enabled, the threshold value of the internal
comparator is the sum of the
Start value Add
and
Start value
settings. This allows a
temporal increase or decrease of the level detector depending on the sign and value
of the
Start value Add
setting, for example, when the emergency start is activated.
If, for example,
Start value
is 100,
Start value Add
is 20 and the ENA_ADD input is
active, the input signal needs to rise above 120 before MAPGAPC operates.
4.11.6 Signals
4.11.6.1 MAPGAPC Input signals
Table 1046: MAPGAPC Input signals
Name Type Default Description
AI_VALUE FLOAT32 0.0 Analogue input value
BLOCK BOOLEAN 0=False Block signal for acti-
vating the blocking
mode
ENA_ADD BOOLEAN 0=False Enable start added
4.11.6.2 MAPGAPC Output signals
Table 1047: MAPGAPC Output signals
Name Type Description
OPERATE BOOLEAN Operate
START BOOLEAN Start
4.11.7 MAPGAPC Settings
Table 1048: MAPGAPC Group settings (Basic)
Parameter
Values (Range) Unit Step Default Description
Start value -10000.0...10000.0 0.1 0.0 Start value
Start value Add -100.0...100.0 0.1 0.0 Start value Add
Operate delay time 0...200000 ms 100 0 Operate delay time
Table 1049: MAPGAPC Non group settings (Basic)
Parameter
Values (Range) Unit Step Default Description
Operation
1=on
5=off
1=on Operation Off / On
Operation mode
1=Over
2=Under
1=Over Operation mode
Protection functions 1MRS759142 F
1108 REX640
Technical Manual