3.20.1.3 Minimum pulse timer minutes resolution, two channels TPMGAPC
(ANSI 62TPM)
Identification
Function description IEC 61850
identification
IEC 60617
identification
ANSI/IEEE C37.2
device number
Minimum pulse timer minutes reso-
lution, two channels
TPMGAPC TPM 62TPM
Function block
Figure 124: Function block
Functionality
The minimum pulse timer minutes resolution, two channels, function TPMGAPC
contains two independent timers. The function has a settable pulse length (in
minutes). The timers are used for setting the minimum pulse length for example,
the signal outputs. Once the input is activated, the output is set for a specific
duration using the
Pulse time
setting. Both timers use the same setting parameter.
Figure 125: A = Trip pulse is shorter than Pulse time setting, B = Trip pulse is longer
than Pulse time setting
Signals
Table 201: TPMGAPC Input signals
Name Type Default Description
IN1 BOOLEAN 0=False Input 1
IN2 BOOLEAN 0=False Input 2
Table 202: TPMGAPC Output signals
Name Type Description
OUT1 BOOLEAN Output 1 status
OUT2 BOOLEAN Output 2 status