3.17.4.4 Signals
RESUTCTR Input signals
Table 135: RESUTCTR Input signals
Name Type Default Description
URES SIGNAL - Residual voltage
RESUTCTR Output signals
Table 136: RESUTCTR Output signals
Name Type Description
IRES_MEAS SIGNAL Residual current, measured
IRES_MEAS_DR SIGNAL Residual current, measured,
for disturbance recorder
3.17.4.5 RESUTCTR Settings
Table 137: RESUTCTR Non group settings (Basic)
Parameter Values (Range) Unit Step Default Description
Primary current 1.0...15000.0 A 0.1 100.0 Primary current
Secondary voltage 4...240 1 10 Secondary voltage
Amplitude Corr 0.9000...1.1000 0.0001 1.0000 Amplitude correc-
tion
Angle correction -8.0000...8.0000 deg 0.0001 0.0000 Angle correction
factor
Table 138: RESUTCTR Non group settings (Advanced)
Parameter Values (Range) Unit Step Default Description
Reverse polarity
0=False
1=True
0=False Reverse the polari-
ty of the residual
measurement
Frequency adaptivi-
ty
0=Disable
1=Enable
0=Disable Frequency adaptivi-
ty selection
3.18 GOOSE function blocks
GOOSE function blocks are used for connecting incoming GOOSE data to
application. They support BOOLEAN, Dbpos, Enum, FLOAT32, INT8 and INT32 data
types.
Common signals
The VALID output indicates the validity of received GOOSE data, which means in
case of valid, that the GOOSE communication is working and received data quality
bits (if configured) indicate good process data. Invalid status is caused either by
Basic functions
1MRS759142 F
204 REX640
Technical Manual