RESTCTR Output signals
Table 124: RESTCTR Output signals
Name Type Description
ALARM BOOLEAN Alarm
WARNING BOOLEAN Warning
IRES_MEAS SIGNAL Residual current, measured
IRES_MEAS_DR SIGNAL Residual current, measured,
for disturbance recorder
3.17.2.5 Settings
RESTCTR Settings
Table 125: RESTCTR Non group settings (Basic)
Parameter Values (Range) Unit Step Default Description
Current input type
2=Current trafo
4=Current sensor
2=Current trafo Type of the current
input
Primary current 1.0...15000.0 A 0.1 100.0 Primary current
Secondary current
1=0.2A
2=1A
3=5A
2=1A Secondary current
Rated secondary
Val
1.000...150.000 mV/Hz 0.001 3.000 Rated Secondary
Value (RSV) ratio
Amplitude Corr 0.9000...1.1000 0.0001 1.0000 Amplitude correc-
tion
Angle correction -8.0000...8.0000 deg 0.0001 0.0000 Angle correction
factor
Table 126: RESTCTR Non group settings (Advanced)
Parameter Values (Range) Unit Step Default Description
Reverse polarity
0=False
1=True
0=False Reverse the polari-
ty of the residual
CT
Frequency adaptivi-
ty
0=Disable
1=Enable
0=Disable Frequency adaptivi-
ty selection
3.17.2.6 Monitored data
Monitored data is available in three locations.
Monitoring> I/O status> Analog inputs
Monitoring> IED status> SMV traffic
Monitoring> IED status> SMV accuracy
Basic functions 1MRS759142 F
196 REX640
Technical Manual