Signals
Table 195: TPGAPC Input signals
Name Type Default Description
IN1 BOOLEAN 0=False Input 1
IN2 BOOLEAN 0=False Input 2
Table 196: TPGAPC Output signals
Name Type Description
OUT1 BOOLEAN Output 1 status
OUT2 BOOLEAN Output 2 status
Settings
Table 197: TPGAPC Non group settings (Basic)
Parameter Values (Range) Unit Step Default Description
Pulse time 0...60000 ms 1 0 Minimum pulse time
3.20.1.2 Minimum pulse timer second resolution, two channels TPSGAPC
(ANSI 62TPS)
Identification
Function description IEC 61850
identification
IEC 60617
identification
ANSI/IEEE C37.2
device number
Minimum pulse timer second reso-
lution, two channels
TPSGAPC TPS 62TPS
Function block
Figure 122: Function block
Functionality
The minimum pulse timer second resolution, two channels, function TPSGAPC
contains two independent timers. The function has a settable pulse length (in
seconds). The timers are used for setting the minimum pulse length for example,
the signal outputs. Once the input is activated, the output is set for a specific
duration using the
Pulse time
setting. Both timers use the same setting parameter.
Basic functions
1MRS759142 F
232 REX640
Technical Manual