Name Type Values (Range) Unit Description
6=FaultDisappeared
7=WaitToComplete
8=CBclosed
9=CycleUnsuccessful
10=Unsuccessful
11=Aborted
INPRO_1 BOOLEAN
0=False
1=True
Reclosing shot in pro-
gress, shot 1
INPRO_2 BOOLEAN
0=False
1=True
Reclosing shot in pro-
gress, shot 2
INPRO_3 BOOLEAN
0=False
1=True
Reclosing shot in pro-
gress, shot 3
INPRO_4 BOOLEAN
0=False
1=True
Reclosing shot in pro-
gress, shot 4
INPRO_5 BOOLEAN
0=False
1=True
Reclosing shot in pro-
gress, shot 5
DISCR_INPRO BOOLEAN
0=False
1=True
Signal indicating that
discrimination time is
in progress
CUTOUT_INPRO BOOLEAN
0=False
1=True
Signal indicating that
cut-out time is in pro-
gress
SUC_RECL BOOLEAN
0=False
1=True
Indicates a successful
reclosing sequence
UNSUC_CB BOOLEAN
0=False
1=True
Indicates an unsuccess-
ful CB closing
CNT_SHOT1 INT32 0...2147483647 Resetable operation
counter, shot 1
CNT_SHOT2 INT32 0...2147483647 Resetable operation
counter, shot 2
CNT_SHOT3 INT32 0...2147483647 Resetable operation
counter, shot 3
CNT_SHOT4 INT32 0...2147483647 Resetable operation
counter, shot 4
CNT_SHOT5 INT32 0...2147483647 Resetable operation
counter, shot 5
COUNTER INT32 0...2147483647 Resetable operation
counter, all shots
SHOT_PTR INT32 1...7 Shot pointer value
MAN_CB_CL BOOLEAN
0=False
1=True
Indicates CB manual
closing during reclosing
sequence
SOTF BOOLEAN
0=False
1=True
Switch-onto-fault
DARREC Enum
1=on
2=blocked
3=test
4=test/blocked
5=off
Status
Control functions 1MRS759142 F
1694 REX640
Technical Manual