Control and status indication facilities are implemented in the same package
with CBXCBR, DCXSWI and ESXSWI. When primary components are controlled in
the energizing phase, for example, the correct execution sequence of the control
commands must be ensured. This can be achieved, for example, with interlocking
based on the status indication of the related primary components. The interlocking
on substation level can be applied using the IEC 61850 GOOSE messages between
feeders.
Control and interlocking via GOOSE messages
REF 615 REF 615 REF 615
REF 615
Figure 830: Status indication-based interlocking via the GOOSE messaging
9.1.6 Signals
9.1.6.1 CBXCBR Input signals
Table 1456: CBXCBR Input signals
Name Type Default Description
POSOPEN BOOLEAN 0=False Signal for open po-
sition of apparatus
from I/O
POSCLOSE BOOLEAN 0=False Signal for close po-
sition of apparatus
from I/O
ENA_OPEN BOOLEAN 1=True Enables opening
ENA_CLOSE BOOLEAN 1=True Enables closing
Table continues on the next page