∫
Integrator box
Amplifier
Protection relay
Rogowski
coil
I
I>
Figure 251: Rogowski coil measurement arrangement
It is also possible to feed shaft current, measured with CT, directly to the relay
current input. Proper signal levels need to be ensured for reaching acceptable
operation accuracy.
Setting
Alarm start value
and
Operate start value
The current level that causes damage to bearings depends on the contact surface of
the bearings. Current densities over 0.1 A/mm
2
start to damage the bearings. This
can be generalized so, that currents over 1 A can be considered harmful. Therefore,
the recommended setting for
Operate start value
is 0.5 A and for
Alarm start value
0.25 A. Both values are set in primary amperes.
4.1.12.7 Signals
GSLPTOC Input signals
Table 496: GSLPTOC Input signals
Name Type Default Description
ISHFT SIGNAL - Analog input
BLOCK BOOLEAN 0=False Block signal for all bi-
nary outputs
GSLPTOC Output signals
Table 497: GSLPTOC Output signals
Name Type Description
OPERATE BOOLEAN Operate
START BOOLEAN Start
ALARM BOOLEAN Alarm
Protection functions 1MRS759142 F
438 REX640
Technical Manual