The tag activation, deactivation and status information can be configured through
the Graphical Display Editor (GDE).
3.20.15.6 Signals
HLTGAPC Input signals
Table 255: HLTGAPC Input signals
Name Type Default Description
TAG_ON_OFF BOOLEAN 0=False Toggles the local tag
on/off with each ris-
ing edge
HLTGAPC Output signals
Table 256: HLTGAPC Output signals
Name Type Description
TAG_ON BOOLEAN Hotline tag active
TAG_OFF BOOLEAN Hotline tag is not active
3.20.15.7 HLTGAPC Settings
Table 257: HLTGAPC Non group settings (Basic)
Parameter Values (Range) Unit Step Default Description
Operation
1=on
5=off
1=on Operation Off / On
Remote tag mode
1=Untag Rem only
2=Untag Loc or
Rem
1=Untag Rem only Deactivation mode
for remotely set
hotline tag
3.20.15.8 HLTGAPC Monitored data
Table 258: HLTGAPC Monitored data
Name Type Values (Range) Unit Description
TAG_SOURCE Enum
0=None
1=Local
2=Remote
Source of active hotline
tag
HLTGAPC Enum
1=on
2=blocked
3=test
4=test/blocked
5=off
Status
Basic functions 1MRS759142 F
274 REX640
Technical Manual