DOPPDPR Input signals
Table 1002: DOPPDPR Input signals
Name Type Default Description
I3P SIGNAL - Three-phase currents
U3P SIGNAL - Three-phase voltages
BLOCK BOOLEAN 0=False Block signal for acti-
vating the blocking
mode
DOPPDPR Output signals
Table 1003: DOPPDPR Output signals
Name Type Description
OPERATE BOOLEAN Operate
START BOOLEAN Start
4.8.2.8 DOPPDPR Settings
Table 1004: DOPPDPR Group settings (Basic)
Parameter
Values (Range) Unit Step Default Description
Start value 0.01...2.00 xSn 0.01 1.00 Start value
Operate delay time 40...300000 ms 10 40 Operate delay time
Directional mode
2=Forward
3=Reverse
2=Forward Directional mode
Power angle -90...90 deg 1 0 Adjustable angle
for power
Table 1005: DOPPDPR Non group settings (Basic)
Parameter
Values (Range) Unit Step Default Description
Operation
1=on
5=off
1=on Operation On/Off
Measurement
mode
1=PhsA, PhsB, PhsC
2=Arone
3=Pos Seq
4=PhsAB
5=PhsBC
6=PhsCA
7=PhsA
8=PhsB
9=PhsC
3=Pos Seq Selection of power
calculation method
Protection functions 1MRS759142 F