11.2.1.3 RI and RD-type inverse-time characteristics
The RI-type simulates the behavior of electromechanical relays. The RD-type is an
earth-fault specific characteristic.
The RI-type is calculated using the formula
t s
k
I
I
[ ]
. .
=
×
>
0 339 0 236
(Equation 395)
The RD-type is calculated using the formula
t s
I
k I
[ ] . .= ×
× >
5 8 1 35 In
(Equation 396)
t[s] Operate time (in seconds)
k Set
Time multiplier
I Measured current
I> Set
Start value
1MRS759142 F General function block features
REX640
Technical Manual
1881