ABB RELION REX640 - PHIPTOC Settings; 4.1.1.11 Monitored data; PHLPTOC Monitored data

ABB RELION REX640
1960 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Parameter Values (Range) Unit Step Default Description
Curve parameter C 0.02...2.00 0.01 2.00 Parameter C for
customer program-
mable curve
Curve parameter D 0.46...30.00 0.01 29.10 Parameter D for
customer program-
mable curve
Curve parameter E 0.0...1.0 0.1 1.0 Parameter E for
customer program-
mable curve
Table 380: PHHPTOC Non group settings (Advanced)
Parameter Values (Range) Unit Step Default Description
Minimum operate
time
20...60000 ms 1 20 Minimum operate
time for IDMT
curves
Reset delay time 0...60000 ms 1 20 Reset delay time
Measurement
mode
1=RMS
2=DFT
3=Peak-to-Peak
2=DFT Selects used meas-
urement mode
PHIPTOC Settings
Table 381: PHIPTOC Group settings (Basic)
Parameter
Values (Range) Unit Step Default Description
Start value 0.10...40.00 xIn 0.01 1.00 Start value
Start value Mult 0.8...10.0 0.1 1.0 Multiplier for scal-
ing the start value
Operate delay time 20...300000 ms 10 20 Operate delay time
Table 382: PHIPTOC Non group settings (Basic)
Parameter
Values (Range) Unit Step Default Description
Operation
1=on
5=off
1=on Operation Off / On
Num of start pha-
ses
1=1 out of 3
2=2 out of 3
3=3 out of 3
1=1 out of 3 Number of phases
required for oper-
ate activation
Table 383: PHIPTOC Non group settings (Advanced)
Parameter
Values (Range) Unit Step Default Description
Reset delay time 0...60000 ms 1 20 Reset delay time
4.1.1.11 Monitored data
PHLPTOC Monitored data
Table 384: PHLPTOC Monitored data
Name
Type Values (Range) Unit Description
START_DUR FLOAT32 0.00...100.00 % Ratio of start time / op-
erate time
PHLPTOC Enum
1=on
Status
Protection functions 1MRS759142 F
342 REX640
Technical Manual