Table 420: PHPVOC Non group settings (Basic)
Parameter Values (Range) Unit Step Default Description
Operation
1=on
5=off
1=on Operation Off / On
Num of start pha-
ses
1=1 out of 3
2=2 out of 3
3=3 out of 3
1=1 out of 3 Number of phases
required for oper-
ate activation
Curve parameter A 0.0086...120.0000 0.0001 28.2000 Parameter A for
customer program-
mable curve
Curve parameter B 0.0000...0.7120 0.0001 0.1217 Parameter B for
customer program-
mable curve
Curve parameter C 0.02...2.00 0.01 2.00 Parameter C for
customer program-
mable curve
Curve parameter D 0.46...30.00 0.01 29.10 Parameter D for
customer program-
mable curve
Curve parameter E 0.0...1.0 0.1 1.0 Parameter E for
customer program-
mable curve
Table 421: PHPVOC Non group settings (Advanced)
Parameter
Values (Range) Unit Step Default Description
Measurement
mode
1=RMS
2=DFT
3=Peak-to-Peak
2=DFT Selects used meas-
urement mode
Control mode
1=Voltage control
2=Input control
3=Voltage and in-
put Ctl
4=No Volt depend-
ency
1=Voltage control Type of control
Minimum operate
time
40...60000 ms 1 40 Minimum operate
time for IDMT
curves
Reset delay time 0...60000 ms 1 20 Reset delay time
4.1.3.9 PHPVOC Monitored data
Table 422: PHPVOC Monitored data
Name
Type Values (Range) Unit Description
START_DUR FLOAT32 0.00...100.00 % Ratio of start time / op-
erate time
EFF_ST_VAL_A FLOAT32 0.00...50.00 xIn Effective start value for
phase A
EFF_ST_VAL_B FLOAT32 0.00...50.00 xIn Effective start value for
phase B
EFF_ST_VAL_C FLOAT32 0.00...50.00 xIn Effective start value for
phase C
PHPVOC Enum
1=on
2=blocked
3=test
4=test/blocked
Status
1MRS759142 F Protection functions
REX640
Technical Manual
377