ILTCTR Output signals
Table 119: ILTCTR Output signals
Name Type Description
ALARM BOOLEAN Alarm
WARNING BOOLEAN Warning
I3P SIGNAL Three-phase currents
IRES_CLC SIGNAL Residual current, calculated
IRES_CLC_DR SIGNAL Residual current, calculated,
for disturbance recorder
IL1_DR SIGNAL Phase current IL1 for disturb-
ance recorder
IL2_DR SIGNAL Phase current IL2 for disturb-
ance recorder
IL3_DR SIGNAL Phase current IL3 for disturb-
ance recorder
NPS_DR SIGNAL Negative sequence current
for disturbance recorder
PPS_DR SIGNAL Positive sequence current for
disturbance recorder
3.17.1.5 Settings
ILTCTR Settings
Table 120: ILTCTR Non group settings (Basic)
Parameter Values (Range) Unit Step Default Description
Current input type
2=Current trafo
4=Current sensor
2=Current trafo Type of the current
input
Primary current 1.0...15000.0 A 0.1 100.0 Rated primary cur-
rent
Secondary current
2=1A
3=5A
2=1A Rated secondary
current
Rated secondary
Val
1.000...150.000 mV/Hz 0.001 3.000 Rated Secondary
Value (RSV) ratio
Amplitude Corr A 0.9000...1.1000 0.0001 1.0000 Phase A amplitude
correction factor
Amplitude Corr B 0.9000...1.1000 0.0001 1.0000 Phase B amplitude
correction factor
Amplitude Corr C 0.9000...1.1000 0.0001 1.0000 Phase C amplitude
correction factor
Angle Corr A -8.0000...8.0000 deg 0.0001 0.0000 Phase A angle cor-
rection factor
Angle Corr B -8.0000...8.0000 deg 0.0001 0.0000 Phase B angle cor-
rection factor
Angle Corr C -8.0000...8.0000 deg 0.0001 0.0000 Phase C angle cor-
rection factor