Table 62: Optional operation modes for setting group selection
SG operation mode Description
Operator (Default) Setting group can be changed with the setting Settings/Set-
ting group/Active group. Value of the SG_LOGIC_SEL out-
put is FALSE.
Logic mode 1 Setting group can be changed with binary inputs
(BI_SG_2...BI_SG_6). The highest TRUE binary input de-
fines the active setting group. Value of the SG_LOGIC_SEL
output is TRUE.
Logic mode 2
Setting group can be changed with binary inputs where
BI_SG_4 is used for selecting setting groups 1–3 or 4–6.
When binary input BI_SG_4 is FALSE, setting groups 1–3 are
selected with binary inputs BI_SG_2 and BI_SG_3. When
binary input BI_SG_4 is TRUE, setting groups 4–6 are selec-
ted with binary inputs BI_SG_5 and BI_SG_6. Value of the
SG_LOGIC_SEL output is TRUE.
For example, six setting groups can be controlled with three binary inputs.
SG
operation mode
is set to "Logic mode 2" and inputs BI_SG_2 and BI_SG_5 are
connected together the same way as inputs BI_SG_3 and BI_SG_6.
Table 63: SG operation mode = "Logic mode 1"
Input
BI_SG_2 BI_SG_3 BI_SG_4 BI_SG_5 BI_SG_6 Active group
FALSE FALSE FALSE FALSE FALSE 1
TRUE FALSE FALSE FALSE FALSE 2
any TRUE FALSE FALSE FALSE 3
any any TRUE FALSE FALSE 4
any any any TRUE FALSE 5
any any any any TRUE 6
Table 64: SG operation mode = "Logic mode 2"
Input
BI_SG_2 BI_SG_3 BI_SG_4 BI_SG_5 BI_SG_6 Active group
FALSE FALSE FALSE any any 1
TRUE FALSE FALSE any any 2
any TRUE FALSE any any 3
any any TRUE FALSE FALSE 4
any any TRUE TRUE FALSE 5
any any TRUE any TRUE 6
Setting group 1 can be copied to any other or all groups from HMI (Copy group 1).
Basic functions
1MRS759142 F
132 REX640
Technical Manual