3.19.5.2 Functionality
The GOOSE data health function T_HEALTH evaluates enumerated data of “Health
data attribute. This function block can only be used with GOOSE.
The IN input can be connected to GOOSERCV_ENUM function block, which is
receiving the LD0.LLN0.Health.stVal data attribute sent by another device.
The outputs OK, WARNING and ALARM are extracted from the enumerated input value.
Only one of the outputs can be active at a time. In case the GOOSERCV_ENUM
function block does not receive the value from the sending device or it is invalid, the
default value (0) is used and the ALARM is activated in the T_HEALTH function block.
3.19.5.3 Signals
Table 163: T_HEALTH Input signals
Name Type Default Description
IN1 Any 0 Input signal
Table 164: T_HEALTH Output signals
Name Type Description
OK BOOLEAN Output signal
WARNING BOOLEAN Output signal
ALARM BOOLEAN Output signal