3.22.2.3 Signals
Table 317: DIVR Input signals
Name Type Default Description
REAL_IN1 FLOAT32 0 Real input 1
REAL_IN2 FLOAT32 0 Real input 2
Table 318: DIVR Output signals
Name Type Description
REAL_OUT IN1 Real output
VALID BOOLEAN Output validity
3.22.3 Real multiplication MULR
3.22.3.1 Function block
Figure 174: Function block
3.22.3.2 Functionality
The real multiplication function MULR multiplies the real input REAL_IN1 by the real
input REAL_IN2 together. MULR executes the equation
REAL_OUT = REAL_IN1 x REAL_IN2
If the value of the product is outside the range, then the output quality is set as
bad and VALID is set to FALSE. The minimum negative product value is restricted to
-2097152.000 and the maximum positive product value is restricted to 2097152.000.
3.22.3.3 Signals
Table 319: MULR Input signals
Name Type Default Description
REAL_IN1 FLOAT32 0 Real input 1
REAL_IN2 FLOAT32 0 Real input 2
Table 320: MULR Output signals
Name Type Description
REAL_OUT FLOAT32 Real output
VALID BOOLEAN Output validity
1MRS759142 F Basic functions
REX640
Technical Manual
301