6.5 Fuse failure supervision SEQSPVC (ANSI VCM, 60)
6.5.1 Identification
Function description IEC 61850
identification
IEC 60617
identification
ANSI/IEEE C37.2
device number
Fuse failure supervision SEQSPVC FUSEF VCM, 60
6.5.2 Function block
Figure 757: Function block
6.5.3 Functionality
The fuse failure supervision function SEQSPVC is used to block the voltage-
measuring functions when failure occurs in the secondary circuits between the
voltage transformer (or combi sensor or voltage sensor) and protection relay to
avoid misoperations of the voltage protection functions.
SEQSPVC has two algorithms, a negative sequence-based algorithm and a delta
current and delta voltage algorithm.
A criterion based on the delta current and the delta voltage measurements can be
activated to detect three-phase fuse failures which usually are more associated with
the voltage transformer switching during station operations.